Capacitive Voltage Transformer (CVT) in high and medium voltage system cannot be used for harmonic voltage measurement. A new method making use of capacitive taps in Current Transformer (CT) bushings is recommended here, this method can achieve the good precision of harmonic voltage measurement. Attention to Potential Transformer (PT) should be paid in special cases such as a resistor or non-linear resistor is connected across the neutral point on primary side and ground. In such a case, the harmonic voltage measurement cannot reflect the real distortion of the system voltage.
机译:高中电压系统(CVT)的电容电压互感器(CVT)不能用于谐波电压测量。在此推荐使用电流互感器(CT)衬套中的电容水龙头的新方法,这种方法可以实现谐波电压测量的良好精度。注意潜在的变压器(PT)应在特殊情况下支付,例如电阻器或非线性电阻在初级侧和地面上的中性点上连接。在这种情况下,谐波电压测量不能反映系统电压的实际失真。