摘要

A new cleanliness classification system for air-handling components and systems was officially launched in Finland at the end of September 2001. This paper describes the test procedure and summarizes all the test methods available for the classification tests and product development as well as the limit values. The main parameters are amount of dust, amount of oil residuals on metal surfaces, and odour emission. The limit value for surface dust is 0.5 g/m~2 in new, uninstalled components and the limit value for oil residuals is 50 mg/m~2 or 300 mg/m~2 depending on the type of the component. There are also some additional test methods, such as a measuring method of mineral fibres released into airflow and a method for measuring the odour threshold of processing oils. Additional tests are required if the component contains fibrous materials or a new type of lubricant is used in the manufacturing process.
机译:2001年9月底,在芬兰正式启动了一种新的清洁度​​分类系统。本文介绍了测试程序,并总结了分类测试和产品开发以及限制值的所有测试方法。 。主要参数是灰尘的量,金属表面上的油残留量和气味排放量。表面粉尘的极限值为0.5g / m〜2,卸载的组分,油残留物的极限值取决于组分类型的50mg / m〜2或300mg / m〜2。还存在一些额外的测试方法,例如释放到气流中的矿物纤维的测量方法和用于测量加工油的气味阈值的方法。如果组分含有纤维材料或在制造过程中使用新型润滑剂,则需要额外的测试。