首页> 外文会议>日本伝熱シンポジウム >Investigation of Fin Efficiency for Cross-finned Tube Heat Exchangers with Plane Fins
【24h】

Investigation of Fin Efficiency for Cross-finned Tube Heat Exchangers with Plane Fins

机译:用平面翅片跨翅管热交换器翅片效率的研究

获取原文

摘要

In this study, the sensible heat fin efficiency for cross-finned tube heat exchangers with plane fins which are used in air conditioning appliances mainly was investigated. The fin efficiency of single row various fin shapes were calculated and compared with Schmidt's formula. Consequently, the calculated results were less than Schmidt's formula within 10% because of a difference of rows. The modification of this formula agreed with calculation within 5% is suggested. Moreover, an effect of the temperature difference between super heated and condensation region on the fin efficiency was investigated. As it turned out the estimate expression used by the difference between inlet air, condensation and super heated temperature was suggested.
机译:在这项研究中,主要研究了主要用于空调器具的平面翅片的跨翅管热交换器的明智热翅片效率。计算单排各种翅片形状的翅片效率,并与施密特公式进行比较。因此,由于行的差异,计算结果少于10%的施密特公式。提出了在5%内计算的该公式的修改。此外,研究了超热和冷凝区域对鳍效率的温差的影响。如它所知,提出了入口空气,缩合和超加热温度之间使用的估计表达。