Unity power factor can be obtained if phase lock loop (PLL) with droop characteristic is used for grid-connected inverter. However, the non-detection zones (NDZ) of the droop PLL is too wide to satisfy some standard. In order to decrease the NDZ, an improved PLL is proposed, which introduces phase disturbance into the control strategy. The operating principle is analyzed and the selecting rule for phase disturbance parameter is given. The anti-islanding capacity of the droop PLL is obtained and the NDZ of the improved PLL is significant decreased. Moreover, the biggest advantage of the improved PLL is that the quality of grid current is not affected by the phase disturbance. The simulation and experimental results verify that the proposed method is effective in islanding detection.
机译:如果使用下垂特性的锁相环(PLL)用于网格连接的逆变器,则可以获得Unity功率因数。然而,Droop PLL的非检测区域(NDZ)太宽,以满足一些标准。为了减少NDZ,提出了一种改进的PLL,这引入了对照策略的相位扰动。分析了操作原理,并给出了相位扰动参数的选择规则。获得了下垂PLL的反孤岛能力,并且改进的PLL的NDZ显着降低。此外,改进PLL的最大优点是电网电流的质量不受相位扰动的影响。模拟和实验结果验证了所提出的方法在岛屿检测方面是有效的。