首页> 外文会议>Power Electronics and Motion Control Conference (IPEMC), 2012 7th International >Anti-islanding performance of grid-connected inverters based on frequency droop PLL
【24h】

Anti-islanding performance of grid-connected inverters based on frequency droop PLL

机译:基于频率下降锁相环的并网逆变器的抗孤岛性能

获取原文
获取外文期刊封面目录资料

摘要

Unity power factor can be obtained if phase lock loop (PLL) with droop characteristic is used for grid-connected inverter. However, the non-detection zones (NDZ) of the droop PLL is too wide to satisfy some standard. In order to decrease the NDZ, an improved PLL is proposed, which introduces phase disturbance into the control strategy. The operating principle is analyzed and the selecting rule for phase disturbance parameter is given. The anti-islanding capacity of the droop PLL is obtained and the NDZ of the improved PLL is significant decreased. Moreover, the biggest advantage of the improved PLL is that the quality of grid current is not affected by the phase disturbance. The simulation and experimental results verify that the proposed method is effective in islanding detection.
机译:如果将具有下垂特性的锁相环(PLL)用于并网逆变器,则可以获得单位功率因数。但是,下垂PLL的非检测区(NDZ)太宽,无法满足某些标准。为了减小NDZ,提出了一种改进的PLL,将相位扰动引入控制策略。分析了工作原理,给出了相位干扰参数的选择原则。获得了下垂PLL的抗孤岛能力,改进后的PLL的NDZ显着降低。而且,改进的PLL的最大优点是电网电流的质量不受相位干扰的影响。仿真和实验结果验证了该方法在孤岛检测中的有效性。