This paper studied the leakage current of insulator strings applied with operating stress during icing regime and evaluated the insulator string's icing status based on leakage current characteristic. Artificial icing test were conducted on one kind of widely used ceramic insulator. Leakage current waveforms of the insulator string during the icing regime were recorded by leakage current monitoring system. The relationship between the maximum leakage current and the icing duration was studied. Power Spectral of the maximum leakage current series of every 20 minutes were analyzed. It was found that the power spectral of principal frequencies such as 50 Hz, 150 Hz and 250 Hz rise with the icing duration and relate closely to the icing thickness on insulator strings. Fitting curves of the power spectral density with the icing duration were given. It provided a good approach to evaluate the insulator strings' icing status.
机译:本文研究了在结冰状态期间采用工作应力施加的绝缘子串的漏电流,并根据漏电流特性评估绝缘子串的结冰状态。在一种广泛使用的陶瓷绝缘体上进行人造糖霜试验。通过漏电流监测系统记录结冰状态期间绝缘体串的漏电流波形。研究了最大漏电流与结冰持续时间之间的关系。分析了每20分钟的最大漏电流系列的功率谱。发现主要频率的功率谱,例如50Hz,150Hz和250Hz的掺入持续时间升高,并且与绝缘体串上的糖束厚度紧密相关。给出了具有结冰持续时间的功率谱密度的拟合曲线。它提供了一种良好的方法来评估绝缘子串的结冰状态。