摘要

The paper deals with the results of investigations performed in order to verify whether diagnostic tests, based on Partial Discharge Height Distribution (PDHD) analysis, are able to identify the causes of deterioration and to guide the repair of the insulation system of HV rotating machine stator windings. The insulation system of a turbogenerator was tested after a breakdown occurred in service. Partial Discharge (PD) measurements were performed both on the windings and on single coils. The analysis of the results of PD measurements evidenced that the breakdown was due to a defective impregnation of the winding.
机译:本文涉及进行研究结果,以验证基于局部放电高度分布(PDHD)分析的诊断测试,能够识别恶化的原因,并指导HV旋转机定子的绝缘系统的修复绕组。在服务中发生击穿后测试涡轮机的绝缘系统。在绕组和单线线圈上进行局部放电(PD)测量。 PD测量结果的分析证明了崩溃是由于绕组缺陷。