首页> 外文会议>National Heat Transfer Conference >EXPERIMENTAL STUDY ON THE EFFECT OF EVAPORATIVE COOLING ON THE THERMAL RESPONSE OF COMMERCIAL FIRE SPRINKLERS
【24h】

EXPERIMENTAL STUDY ON THE EFFECT OF EVAPORATIVE COOLING ON THE THERMAL RESPONSE OF COMMERCIAL FIRE SPRINKLERS

机译:蒸发冷却对商用消防喷水隆头热响应影响的实验研究

获取原文

摘要

A new model to predict the activation time of fire suppression sprinklers is validated experimentally. The model extends the range of applicability of previous formulations to allow for the presence of water droplets in the fire plume. The presence of water droplets in the hot gas flow is due to the activation of the first sprinkler. The droplets are carried by the gas and deposited on the surrounding sprinklers, where they evaporate. The vaporization process cools the sprinklers and this causes a delay in their activation. Three sets of commercially available sprinklers are tested under three different boundary conditions. The experimental results show good agreement with the predictions of the model within the uncertainties associated with the measurements. The influence of the sprinkler frame orientation on the evaporative cooling is also discussed in this paper.
机译:通过实验验证预测灭火喷水器激活时间的新模型。该模型扩展了先前制剂的适用范围,以允许在火羽毛中存在水滴。在热气流中存在水滴是由于第一喷水隆起的激活。液滴由气体承载并沉积在周围的喷洒器上,在那里它们蒸发。汽化过程冷却喷洒器,这导致其激活延迟。在三种不同的边界条件下测试三组市售洒水喷头。实验结果表明,与与测量相关的不确定性内的模型的预测表现出良好的一致性。本文还讨论了喷洒框架方向对蒸发冷却的影响。