首页> 外文会议>International Congress on Sound and Vibration >MEASUREMENT AND ANALYSIS OF NOISE CHARACTERISTICS IN A 1000KV AC SUBSTATION
【24h】

MEASUREMENT AND ANALYSIS OF NOISE CHARACTERISTICS IN A 1000KV AC SUBSTATION

机译:1000kV交流变电站中噪声特性的测量与分析

获取原文

摘要

Audible noise characteristics of UHV substations are paramount for the noise prediction and reduction. In this paper, the noise level and spectrum distribution of the transformers, high-voltage reactors and electrified structure, and the noise level at the boundary of the 1000kV AC substation are measured and analyzed in detail. The results also show that the sound pressure level of the transformers and high-voltage reactors was 65.7 ~74.5 dB(A) and 69.7 ~79.1 dB(A), respectively. The maximum value of the electrified structure is 61.6 dB(A) and the noise at the boundary of the substation is closely related to the layout of the main acoustic sources.
机译:用于噪声预测和减少的UHV变电站的可听噪声特性是至关重要的。本文详细测量和分析了变压器,高压反应器和电气化结构的噪声水平和光谱分布,以及1000kV AC变电站边界处的噪声水平。结果还表明,变压器和高压反应器的声压级分别为65.7〜74.5dB(a)和69.7〜79.1dB(a)。电化结构的最大值为61.6dB(a),并且变电站边界处的噪声与主要声学来源的布局密切相关。