Impact of DC grid topology on transient stability of HVDC-segmented power system

机译:直流网格拓扑对高压型电力系统瞬态稳定性的影响

获取原文

摘要

This paper compares the effects of ring, radial and interconnected DC grid topologies on the transient stability of a segmented 15 - bus electric grid for different HVDC schemes. For this purpose, three HVDC convertor technologies and four HVDC station configurations are considered. A three phase AC bus fault is applied and the rotor angle disturbance is analyzed. The results show that the transient stability is dependent on the topology for bipolar configuration of line commutated current source and capacitor commutated convertor technologies. For rest of the HVDC schemes, transient stability is independent of the topology used.
机译:本文比较了环,径向和互连的直流栅极拓扑对不同HVDC方案的分段15总线电网的瞬态稳定性的影响。为此目的,考虑了三种HVDC转换器技术和四个HVDC站配置。施加三相交流总线故障,分析转子角度干扰。结果表明,瞬态稳定性取决于线路换向电流源和电容换向器技术的双极配置的拓扑。对于HVDC方案的其余部分,瞬态稳定性与所使用的拓扑无关。