首页> 外文会议>Annual North American Power Symposium >Zero-sequence impedance of overhead transmission lines with discontinuous ground wire
【24h】

Zero-sequence impedance of overhead transmission lines with discontinuous ground wire

机译:具有不连续地线的零架传输线的零序阻抗

获取原文

摘要

The authors give a method to calculate the zero-sequence impedance of a transmission line having ground wires that are not continuous or are not connected to the station grounds at the end of the line. The calculated values are compared with the measured zero-sequence impedance of a line. The authors observe that for transmission lines having discontinuous ground wires, the actual zero-sequence impedance is different from the zero-sequence impedance of the line calculated with the classical methods and considering either no ground wire or continuous ground wire. This difference is significant if the ground wire is of ACSR conductor. The method given for calculating the zero-sequence impedance of a transmission line with discontinuous ground wire gives more accurate results, which are close to the measured values.
机译:作者给出了一种方法来计算具有接地线的传输线的零序阻抗,该接地线不连续或未连接到线的末端的站地。将计算的值与线的测量零序阻抗进行比较。作者观察到,对于具有不连续地线的传输线,实际的零序阻抗与用经典方法计算的线的零序阻抗不同,并且考虑无接地线或连续地线。如果接地线是ACSR导体,则这种差异是显着的。给出用于计算具有不连续接地线的传输线的零序阻抗的方法给出了更准确的结果,其接近测量值。