Current Carrying Capacity of an Earthing Switch for a Generator Circuit Breaker

机译:发电机断路器的接地开关的电流承载能力

获取原文

摘要

In this study we present the contact system of an earthing switch used in a Generator Circuit Breaker (GCB) System focusing on the current carrying capacity. For this special application the contact system is required to withstand short-circuit currents of 210kA_(rms) @ 1s. The safe and reliable operation of the system is achieved thanks to a tulip contact with silver plated contact fingers. The focus of this study is the relationship between the total force of the contact, the welding current and the contact resistance. During operation, the resulting force of the contact, due to the electromagnetic forces, can rise from a nominal contact force minor than 50N to peaks of more than 1kN. In this study, a FEA simulation of the total contact forces is presented. The simulation results were then validated by means of dedicated experimental tests. The experimental campaign enabled the determination of the current carrying capacity and the welding threshold currents over a wide range of contact forces. Thanks to this new development, the presented earthing switch was successfully type tested (acc. to IEC 62271-1) at a peak current of 575 kA.
机译:在这项研究中,我们介绍了在发电机断路器(GCB)系统中使用的接地开关的接触系统,其专注于电流承载能力。对于此特殊应用,需要接触系统以耐受210kA_(RMS)@ 1s的短路电流。由于郁金香接触与镀银接触手指的郁金香接触,实现了系统的安全可靠运行。本研究的重点是接触总力与接触电阻之间的关系。在操作期间,由于电磁力而导致的接触的所得力可以从较小50n的标称接触力升高到超过1kN的峰。在这项研究中,提出了总接触力的FEA模拟。然后通过专用的实验测试验证模拟结果。实验活动使得能够在宽范围的接触力上确定电流承载能力和焊接阈值电流。由于这一新的开发,在575 kA的峰值电流下成功键入测试(ACC。至IEC 62271-1)。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号