Models have been presented to describe the discharge processes which occur when a steep-front, intense voltage pulse is injected onto an open wire transmission line in air. Measurements made to evaluate these models are reported. The experimental data include transient voltage and current on the open wire, photographs of the discharge which forms at the wire and between the wire and ground, and maps of the transient electric field at the ground plane. Variables include voltage, length and size of the wire, height of the wire above the ground plane and duration of the voltage pulse. These data provide an empirical model for the pulsed corona, since V-I behavior under a range of conditions is presented in convenient graphical form. In addition, several characteristics included in theoretical models are examined in terms of the data. The importance of the diffuse corona (glow) component in supporting the voltage at the wire is evaluated. Ground field mapping is shown to be a useful diagnostic tool.
机译:已经提出了模型来描述当陡峭的前部强度脉冲喷射到空气中的开路传输线上时发生的放电过程。报告了评估这些模型的测量。实验数据包括开路线上的瞬态电压和电流,放电的照片在电线和线和地之间形成的拍摄,以及地面平面处的瞬态电场的图。变量包括电线的电压,长度和尺寸,电线高度在接地平面上方和电压脉冲的持续时间。这些数据为脉冲电晕提供了一个经验模型,因为在一系列条件下的V-I行为以方便的图形形式呈现。此外,在数据方面检查了理论模型中包含的若干特性。评估漫反射电晕(发光)部件在支撑线上的电压时的重要性。地面场映射被显示为一个有用的诊断工具。