The behavior of line protection device with line selection function after single-phase grounding fault occurred in non-effectively grounded system is analyzed. After the fault line was selected and tripped, due to the long attenuation time of zero sequence voltage, the device misjudged that the fault was not removed, and wrongly reclosed the fault line, which led to the further development of the fault. In this paper, the voltage recovery process after fault is removed is analyzed and verified by simulation test. Finally, considering the influence of voltage recovery process, an optimal algorithm applicable for various types of line selection devices is proposed to accurately judge whether the fault is removed after the line is selected and tripped, and to improve the operation accuracy of the whole process of single-phase grounding fault.
机译:分析了在非有效接地系统中发生单相接地故障后线选择功能的线保护装置的行为。选择断层线并跳闸后,由于零序电压的长衰减时间,设备误判了故障未被删除,并且错误地关注故障线,这导致了故障的进一步发展。在本文中,通过仿真测试分析并验证了故障后的电压恢复过程。最后,考虑到电压恢复过程的影响,提出了一种适用于各种类型的线路选择装置的最佳算法,以准确判断在线选择和跳闸后是否拆除故障,并提高整个过程的操作精度单相接地故障。