首页> 外文会议>Electrical Engineering Faculty Conference >Investigation of the Relay Protection Operation and the Electrical Safety at the Presence of Predominant Cable Part in Medium Voltage Power Lines
【24h】

Investigation of the Relay Protection Operation and the Electrical Safety at the Presence of Predominant Cable Part in Medium Voltage Power Lines

机译:在中压力线上存在主要电缆部分的继电器保护操作和电气安全的研究

获取原文

摘要

In the medium voltage power lines there is a tendency of enlargement of the cable part. This in turn leads to increase of the earth-fault currents. The practical experience has shown that it is important to consider that enlargement when designing the grounding of the neutral of mixed or cable power lines for medium voltage (normally through an active resistance). The value of the earth-fault current Ig has to be limited in view of limitation the level of the overvoltages and the damages of the equipment, the requirements for the selectiveness and the sensitiveness of the relay protection, the permissible touch Ut and step Us voltages at the earth-fault place. The purpose of the paper is to investigate the operation of the relay protection and the electrical safety in the conditions of enlargement of the share of the cable part in the medium voltage power lines. The values of the possible touch and step voltages have been compared with the maximum permitted values, calculated according to the international IEEE 80-2000 standard Guide for Safety in AC Substation Grounding.
机译:在中压力线中,存在电缆部件的趋势。这反过来导致接地故障电流的增加。实践经验表明,在设计混合或电缆电源线的中性的接地时,重要的是考虑放大,以进行中压(通常通过主动电阻)。地球故障电流的值I g 鉴于限制过电压和设备损坏的水平,必须有限,选择性和继电器保护的敏感性的要求,允许的触摸U t 和迈出了 s 地球故障地方的电压。本文的目的是研究继电器保护的操作和电缆部分在中压力线中的电缆部件份额的条件下的操作。已经将可能的触摸和阶跃电压的值与最大允许值进行比较,根据IEEE 80-2000标准指南计算的AC变电站接地的安全性。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号