Investigation of the Relay Protection Operation and the Electrical Safety at the Presence of Predominant Cable Part in Medium Voltage Power Lines

机译:中压电力线主要电缆部分存在继电保护动作及电气安全的研究

获取原文
获取原文并翻译 | 示例

摘要

In the medium voltage power lines there is a tendency of enlargement of the cable part. This in turn leads to increase of the earth-fault currents. The practical experience has shown that it is important to consider that enlargement when designing the grounding of the neutral of mixed or cable power lines for medium voltage (normally through an active resistance). The value of the earth-fault current Ig has to be limited in view of limitation the level of the overvoltages and the damages of the equipment, the requirements for the selectiveness and the sensitiveness of the relay protection, the permissible touch Ut and step Us voltages at the earth-fault place. The purpose of the paper is to investigate the operation of the relay protection and the electrical safety in the conditions of enlargement of the share of the cable part in the medium voltage power lines. The values of the possible touch and step voltages have been compared with the maximum permitted values, calculated according to the international IEEE 80-2000 standard Guide for Safety in AC Substation Grounding.
机译:在中压电力线中,电缆部分有增大的趋势。这继而导致接地故障电流的增加。实践经验表明,在设计用于中压(通常通过有源电阻)的混合或电缆电源线的中性点接地时,必须考虑增大接地面积。接地故障电流的值I \ n g \ n,以限制过电压的水平和设备的损坏,继电保护的选择性和灵敏性的要求,允许的范围。触摸U \ n t \ n,然后执行步骤U \ n 接地故障处的电压。本文的目的是研究在中压电力线中电缆部分所占份额增加的情况下的继电保护操作和电气安全性。已将可能的接触电压和阶跃电压值与根据国际IEEE 80-2000标准“交流变电站接地安全性指南”计算出的最大允许值进行比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号