Internal Fault Diagnosis and Analysis of a 1000kV Shunt Reactor with Abnormal Ground Current of Iron Core and Clamp

机译:用铁芯和夹具异常接地电流的内部故障诊断与分析

获取原文

摘要

For a fault case of abnormal grounding current in a 1000kV shunt reactor of a UHV substation, firstly, this paper conducted a preliminary analysis of the fault type based on offline oil chromatography data tracking. Secondly, combined with the high-frequency partial discharge live detection and the monitoring results of the partial discharge intensive care system, it was judged that there is no obvious discharge phenomenon inside the shunt reactor. Finally, according to the ground current test and the circuit modeling analysis, it was judged that there was overlap in ground loop between the iron core and clamp, and the overlap resistance was small. After the current-limiting resistors were installed, the ground current was significantly reduced, but the chromatographic data continued to increase, proving that there were still other lapped hot spots inside. Due to disassembly results returned to the factory, the validity of the ground current test and circuit modeling analysis method of the iron core clamp was verified, which can provide reference for fault diagnosis of internal overlap and abnormal ground current of UHV shunt reactors.
机译:对于异常接地电流在UHV变电站的1000kV特并联电抗器中的故障情况下,首先,本文进行了基于离线油色谱数据跟踪故障类型的初步分析。其次,与高频局部放电活检测和局部放电重症监护系统的监测结果相结合,它被判断为有分路电抗器内没有明显的放电现象。最后,根据该接地电流测试和电路建模分析,结果判断出存在在铁芯和夹具之间的接地环路是重叠,并且该重叠阻力是小的。安装了限流电阻后,地面电流显著减少,但色谱数据继续增加,证明仍然有其他的重叠热点内。由于返回工厂拆卸结果,铁芯夹具的接地电流测试和电路建模分析方法的有效性进行了验证,其可提供内部重叠和UHV并联电抗器的异常接地电流的故障诊断参考。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号