Modern substations are implementing Switched Ethernet based IEC 61850-9-2 Process bus communication networks for realizing their protection functions. Packet loss is a common phenomenon and plays a crucial role in the implementation of communication network based time-critical real time protection applications of power system. This paper presents the modeling and simulation of communication based digital distance relay protection scheme using MATLAB. In the first phase, the scheme is tested under various fault types, locations and fault resistance conditions to verify the operating performance of simulated distance relay model. In second phase, it is tested under sampled values packets loss condition to analyze the impact of lost data on the trip time performance of relay model. The result shows that the lost sampled values data in input signals adversely affects the tripping of distance relay.
机译:现代变电站正在实现基于交换式以太网的IEC 61850-9-2过程总线通信网络,以实现其保护功能。丢包是一种普遍现象,在基于通信网络的电力系统时间紧迫实时保护应用的实现中起着至关重要的作用。本文介绍了使用MATLAB的基于通信的数字距离继电保护方案的建模和仿真。在第一阶段,该方案在各种故障类型,位置和故障抵抗条件下进行测试,以验证模拟距离继电器模型的运行性能。第二阶段,在采样值丢包情况下进行测试,分析丢失数据对继电器模型跳闸时间性能的影响。结果表明,输入信号中丢失的采样值数据会对距离继电器的跳闸产生不利影响。