New method for noninvasive measurement of utility harmonic impedance

机译:一种非侵入式测量公用事业谐波阻抗的新方法

获取原文

摘要

The new, noninvasive method of measurement for power system harmonic impedance is presented in the paper. The method is based on the observation of variations of voltage and current harmonics caused by natural load variability. The novelty of the method lays in a way the method rejects segments of data containing insufficient or false information about the identified power system. Segment selection/rejection uses logical conditions applied to RMS values of measured voltage and current. Harmonic impedance of the power grid is then calculated using modified power spectral method. The method was validated in a field test conducted at 30 kV feeder bus of HV/MV substation. Details of the experiment and the results are discussed the paper. Obtained results confirm that the method copes with temporal, band-limited excitation as well as with deep, sudden changes of utility background voltage.
机译:本文提出了一种新的,无创的电力系统谐波阻抗测量方法。该方法基于对自然负载可变性引起的电压和电流谐波变化的观察。该方法的新颖性在于该方法拒绝包含关于所识别的电力系统的信息不足或错误的数据段。段选择/拒绝使用逻辑条件,这些条件适用于所测电压和电流的RMS值。然后,使用改进的功率谱方法计算电网的谐波阻抗。该方法在HV / MV变电站的30 kV馈线母线进行的现场测试中得到了验证。本文详细讨论了实验和结果。所获得的结果证实,该方法可以应对时间带限制的激励,以及公用事业背景电压的急剧变化。