A priori transient stability indicator of islanded power systems using Extended Equal Area Criterion

机译:使用扩展等面积准则的孤岛电力系统的先验暂态稳定指标

获取原文

摘要

This paper demonstrates the use of the Extended Equal Area Criterion (EEAC) to determine if islanded power systems remain transiently stable after the network has been split. Controlled system islanding has been proposed as a method of last resort to avoid a system-wide blackout. Such methods are usually based on some minimum cutset and/or minimum power disturbance criterion but do not specifically take transient stability into account. By developing an a priori transient stability indicator, any splitting methodology can be made more robust as the proposed islands will satisfy static (load, generation balance) as well as transient constraints. If the proposed cutsets result in islands that are transiently unstable, this can be fed back to the splitting methodology and a new cutset and islanding configuration proposed.
机译:本文演示了使用扩展均等面积标准(EEAC)来确定孤岛电力系统在网络分裂后是否保持瞬态稳定。有人提出了控制系统孤岛作为避免系统范围停电的最后手段。这样的方法通常基于一些最小割集和/或最小功率扰动准则,但是没有具体考虑瞬态稳定性。通过开发一个先验的暂态稳定指标,可以将任何分裂方法变得更加健壮,因为建议的孤岛将满足静态(负载,发电平衡)以及暂态约束。如果提出的割集导致岛不稳定,那么可以将其反馈给分割方法,并提出新的割集和岛化配置。