首页> 外文会议>AEIT International Annual Conference >Current endurance testing of termination earth connections for offshore wind farm array cables
【24h】

Current endurance testing of termination earth connections for offshore wind farm array cables

机译:海上风电场阵列电缆终端接地的当前耐久测试

获取原文
获取外文期刊封面目录资料

摘要

Power generation from offshore wind grew vastly in the last 20 years, whilst remaining a relatively young industry without installed technology reaching the end of its design life before advancements are made. Most of the technology of MV (medium voltage) array cable accessories are based on the more experienced land power distribution industry, which faces very different operating conditions and yet are still bound by the same design and test standards. Recently the industry has seen failures related to some “T-connector” terminations on array cables operating offshore at 33 kV, over multiple wind farms and differing cable and termination suppliers. Root cause analysis has been performed by the Authors on one of these windfarms where the main cause of failure was identified as the screen earthing connection within the terminations. As no test methods exist in the relevant international standards, a new current endurance test has been developed to determine the suitability of the installed T-connector earthing methodology, as well as alternative designs. It was found during analysis of the test results that the installed earthing design, although having passed the required short circuit testing to the relevant standards, was not suitable for the design life of the larger cable cross sections used in the project. Two alternative designs, although improved were also not deemed suitable. Two newly designed connections, based on established technology utilising a soldered connection and a mechanical connection, have however, been approved for use.
机译:在过去的20年中,海上风电的发展迅猛,与此同时,仍处于一个相对年轻的行业,没有安装技术就可以达到其设计寿命的极限。 MV(中压)阵列电缆附件的大多数技术都是基于经验更为丰富的陆上配电行业,该行业面临着截然不同的工作条件,但仍受相同的设计和测试标准的约束。最近,该行业已经看到了与在多个风电场以及不同的电缆和端接供应商处以33 kV离岸运行的阵列电缆上的某些“ T型连接器”端接有关的故障。作者已经对这些风电场之一进行了根本原因分析,在这些风电场中,主要故障原因被确定为终端内的屏蔽接地。由于相关国际标准中没有测试方法,因此已经开发了新的当前耐久性测试,以确定已安装的T型连接器接地方法以及替代设计的适用性。在对测试结果进行分析的过程中发现,已安装的接地设计虽然已通过了必要的短路测试并达到了相关标准,但并不适合该项目中使用的较大电缆横截面的设计寿命。尽管进行了改进,但两个替代设计也被认为不适合。然而,已批准使用基于焊接和机械连接的成熟技术的两个新设计的连接。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号