Virtual synchronous generator (VSG) control allows renewable energy sources to behave like traditional synchronous generators under grid disturbances. Under large disturbances, due to the limitation of output current from grid interfacing power electronic converters, VSG controlled sources may output less active power than the emulated SG. Analysis of a single machine infinite bus system shows that the limited current would impair the system transient stability by increasing the acceleration area during a short circuit fault, and decreasing the deceleration area after it. A mitigation method is then proposed to compensate the negative impacts. Experiments with an emulated downscaled multiple machine system are shown to demonstrate the feasibility of the proposed method.
机译:虚拟同步发电机(VSG)控制使可再生能源在电网干扰下的行为类似于传统同步发电机。在较大的干扰下,由于来自电网接口电力电子转换器的输出电流的限制,VSG控制的源可能会输出比仿真SG少的有功功率。对单机无限母线系统的分析表明,有限电流会通过增加短路故障期间的加速面积并减小其后的减速面积而损害系统的瞬态稳定性。然后提出一种缓解方法,以补偿负面影响。模拟缩小规模的多机系统的实验表明了该方法的可行性。