Minimizing Distribution System Power Loss Using Behind-the-Meter Type 3 Generators

机译:使用3型电表发生器将配电系统的功率损耗降至最低

获取原文

摘要

This paper considers power loss reduction in distribution systems by integrating behind-the-meter, type 3 distributed generation (DG) sources. Power loss is estimated using the forward/backward sweep (FBS) method, and the loss reduction is maximized using particle swarm optimization (PSO). Power factor, and DG location and size are used as optimization parameters. The IEEE 33 bus distribution system and PSS SIN-CAL software are used to evaluate the proposed solution. Results presented show that for the same DG penetration in a distribution system, behind-the-meter, type 3 DG sources can significantly reduce power loss. Thus, utilities not only benefit from investment cost savings but also higher efficiency in their distribution systems. Therefore, utilities could give more subsidy to the customers to encourage installing DG sources in optimal locations. DG sources are typically renewable energy sources, so environmental concerns are also mitigated.
机译:本文考虑了通过集成仪表背后的3型分布式发电(DG)电源来降低配电系统中的功率损耗。使用前向/后向扫描(FBS)方法估计功率损耗,并使用粒子群优化(PSO)最大限度地降低损耗。功率因数以及DG的位置和大小用作优化参数。 IEEE 33总线分配系统和PSS SIN-CAL软件用于评估所提出的解决方案。给出的结果表明,对于配电系统中相同的DG渗透,在表后,3型DG源可以显着降低功率损耗。因此,公用事业不仅可以节省投资成本,而且可以提高配电系统的效率。因此,公用事业公司可以向客户提供更多补贴,以鼓励在最佳位置安装危险气体源。 DG来源通常是可再生能源,因此也减轻了对环境的关注。