The starting-up strategy is an important issue for voltage source convert-high voltage direct current (VSC-HVDC) system. If a VSC-HVDC system starts up without any auxiliary system, overvoltage and inrush current will occur. This large overvoltage can cause serious damage on the DC capacitors and this large inrush current at turn-on may destroy the switches in converter. In this paper, starting-up steps in a three-phase two-level VSC-HVDC system is studied with details. The effect of capacitor and inductor values and also circuit breaker closing time on overvoltage and inrush current are investigated attentively. Possible methods for control overvoltage and inrush currents during starting-up are presented, and a comparison has been made between them in terms of power dissipation and cost. Eventually, the best auxiliary starting-up system is selected in terms of costs. Substantial simulations conducted on PSCAD/EMTDC platform.
机译:对于电压源转换高压直流(VSC-HVDC)系统,启动策略是一个重要问题。如果没有任何辅助系统的情况下启动VSC-HVDC系统,则会发生过压和浪涌电流。如此大的过压会严重损坏直流电容器,并且在接通时产生的大浪涌电流可能会损坏转换器中的开关。本文详细研究了三相两电平VSC-HVDC系统的启动步骤。重点研究了电容器和电感器值以及断路器合闸时间对过电压和浪涌电流的影响。提出了在启动过程中控制过电压和浪涌电流的可能方法,并在功耗和成本方面进行了比较。最终,根据成本选择了最佳的辅助启动系统。在PSCAD / EMTDC平台上进行的大量模拟。