首页> 外文会议>IEEE PES Asia-Pacific Power and Energy Engineering Conference >Study on Radio Interference of ±1100 kV Converter Station
【24h】

Study on Radio Interference of ±1100 kV Converter Station

机译:±1100 kV换流站无线电干扰的研究

获取原文

摘要

During the operation of the Ultra-high Voltage DC (UHVDC) transmission project, the radio interference (RI) occurs due to the ignition of the converter valve. If not properly controlled, it will adversely affect the surrounding radio reception. Relying on ±1100 kV Zhundong-Wannan UHVDC project, the wideband model of the converter valve, the transformer, the filter and other equipment is established. And then, the research and calculation of RI levels of the converter station is carried out. The applicability of the radio interference limit of ±500 kV project for ±1100 kV converter station is also checked. The results show that when RI filter is properly installed, the total RI levels of the converter station, the RI levels of the AC line, DC line and neutral line are below the limit. Therefore, the radio interference limit of the ±500 kV converter station can be used as the radio interference limit for ±1100 kV converter station.
机译:在超高压直流(UHVDC)传输项目的运行过程中,由于转换阀的点火而产生了无线电干扰(RI)。如果控制不当,将会对周围的无线电接收产生不利影响。依托±1100 kV准东万南特高压直流输电工程,建立换流阀,变压器,滤波器等设备的宽带模型。然后,进行了换流站RI水平的研究和计算。还检查了±1100 kV换流站的±500 kV项目的无线电干扰限值的适用性。结果表明,正确安装RI滤波器后,换流站的总RI值,交流线,直流线和中性线的RI值均低于限值。因此,可以将±500 kV转换站的无线电干扰限制用作±1100 kV转换站的无线电干扰限制。