A control strategy that enhances power capability of power conditioning (PCU) by injecting maximum rated current during fault ride through (FRT) is presented in this paper. To attain proposed strategy, two active power production situations like high and low are considered. In first situation, if source supply is not able to supply complete generated power to grid, controller applies active power curtailment ensuring maximum rated current isn't surpassed. If peak value of permissible current is not attained then, control scheme determines reactive power injected to a desired value; in next situation. A current injection technique to achieve a contrast amongst positive and negative current to limit output current of PCU to its peak rated value and obviates active power oscillations. A simulation carried out to verify proposed method suggested.
机译:本文介绍了通过在故障骑行期间注入最大额定电流(FRT)来增强功率调节(PCU)功率能力的控制策略。为了获得拟议的策略,考虑了两个高低和低的有效电力生产情况。在第一种情况下,如果源电源无法为网格提供完整的生成电源,则控制器应用有源电源缩减,确保最大额定电流不超过额定电流。如果允许电流的峰值未达到,则控制方案确定注入所需值的无功功率;在下一种情况下。一种当前注射技术,实现正极和负电流之间的对比度,以将PCU的输出电流限制为其峰值额定值并避免有源电力振荡。进行了验证提出的方法的模拟。