A New Defrosting Method Using the Thermosyphon Principles

机译:利用热虹吸原理的除霜新方法

获取原文

摘要

Finned coil air coolers in cold storage rooms need to be regularly defrosted to remove frost witch grows on the tubes and fins during operation and would otherwise lead to deterioration in heat transfer and blockage of air through the coolers. Common methods used in defrosting are use of hot discharge refrigerant gas from the compressor and insertion of electric heaters in the coolers. In Japan water spraying the coolers is very common. None of these methods are energy efficient.To improve energy conservation and efficiency of the cooling system we developed a defrosting method using the principles of the thermosiphon with CO_2 the secondary refrigerant. CO_2 within the cooler is heated with hot brine. The heated CO_2 evaporates but since it is in contact with frost it condenses and while the CO_2 condenses frost is melted.
机译:冷藏室中的翅片盘管空气冷却器需要定期除霜,以消除运行期间在管子和散热片上产生的霜,否则会导致传热变差和空气通过冷却器的阻塞。除霜中常用的方法是使用来自压缩机的热排放制冷剂气体,并将电加热器插入冷却器中。在日本,喷水冷却器非常普遍。这些方法都不是节能的。 为了提高冷却系统的节能性和效率,我们使用热虹吸原理和辅助制冷剂CO_2开发了一种除霜方法。冷却器中的CO_2用热盐水加热。加热的CO_2蒸发,但是由于它与霜接触,因此冷凝,而CO_2冷凝时,霜融化。