EVALUATION AND MODELLING OF ICE RINK ENERGY USAGE 13TH IIR GUSTAV LORENTZEN CONFERENCE

机译:第十三届IIR GUSTAV LORENTZEN会议的冰糖能源评估和建模

获取原文

摘要

Ice rink operation requires significant amounts of energy and a typical single sheet ice rink uses about 1000 MWh per year, where 43% is used by the refrigeration system. To estimate the energy consumption of a refrigeration system, simulation tools have been developed such as Pack Calculation Pro, in parallel with empirical correlations that we have developed for the specific case of ice rinks. In the meantime, continuous energy monitoring and measurements are carried out in many ice rinks, providing the actual energy performance of the installation. Based on a few Swedish ice rinks, the aim of the study was to compare the results obtained with the numerical simulation software and our energy forecast to the actual performances of the refrigeration system. This analysis allowed us to adjust the different models. It led to satisfying results regarding the relative difference between the simulation and measurements for the energy consumption of the refrigeration system and its auxiliaries; less than 10% for a direct expansion CO_2 system and less than 5% for an indirect CO_2 system.
机译:溜冰场的运营需要大量的能源,典型的单层溜冰场每年使用约1000兆瓦时,其中制冷系统使用了43%。为了估算制冷系统的能耗,已经开发了模拟工具(例如Pack Calculation Pro),并结合了我们针对溜冰场的特殊情况开发的经验相关性。同时,在许多溜冰场进行连续的能量监测和测量,以提供设备的实际能量性能。基于瑞典的一些溜冰场,研究的目的是将数值模拟软件获得的结果以及我们的能耗预测与制冷系统的实际性能进行比较。这种分析使我们能够调整不同的模型。对于制冷系统及其辅助设备能耗的仿真与测量之间的相对差异,得出了令人满意的结果。对于直接膨胀的CO_2系统,小于10%,对于间接CO_2系统,小于5%。