Auto-reclose Performance Evaluation on 500kV Transmission Line with Four Circuits on One Tower

机译:一塔四回路500kV输电线路自动重合闸性能评估

获取原文

摘要

The use of transmission line with four circuits on one tower is one way that can be used to minimize the right of way (ROW) issues. There is no study that have discussed the performance of single pole auto-reclose (SPAR) for this type of transmission line, thus it is necessary to study the effect of using this transmission line to SPAR performance, especially study related to the duration of secondary arc. In this paper, the SPAR performance evaluation is performed by varying the fault location on phase, circuit, and transmission line length using transient analysis application. Each of scenario is simulated on phase arrangement which have the lowest and the highest electromagnetic field magnitude. Based on the simulation results, it is known that the use of phase arrangement with the lowest electromagnetic field magnitude will eliminate the probability of SPAR scheme failure for each single phase to ground fault location on this transmission line configuration.
机译:在一塔上使用具有四个电路的传输线是一种可以最大程度地减少通行权(ROW)问题的方法。尚无研究讨论此类传输线的单极自动重合闸(SPAR)性能,因此有必要研究使用该传输线对SPAR性能的影响,尤其是有关次级持续时间的研究。弧。在本文中,通过使用瞬态分析应用程序通过改变相,电路和传输线长度上的故障位置来执行SPAR性能评估。每个场景都是在具有最低和最高电磁场强度的相位安排上进行仿真的。根据仿真结果,众所周知,使用具有最低电磁场强度的相安排将消除此传输线配置上每个单相到接地故障位置的SPAR方案故障的可能性。