For multiple paralleled grid-connected inverters with LCL filter, the internal resonance of the inverters and the parallel resonance among paralleled inverters can be a potential risk for stable and effective operation of the system. In this paper, a Norton equivalent model of the paralleled grid-connected inverters is established. System stability is analyzed based on the close-loop transfer function matrixes. In order to improve the stability of the system, this paper uses an active damping method based on the grid-side current feedback with lead-lag network. The active damping method can suppress the resonance of the inverters and improve the stability of the system. Finally, experimental results are given to verify the analysis made above.
机译:对于具有LCL滤波器的多个并联并网逆变器,逆变器的内部谐振和并联逆变器之间的并联谐振可能会成为系统稳定有效运行的潜在风险。本文建立了并联并网逆变器的诺顿等效模型。基于闭环传递函数矩阵分析系统的稳定性。为了提高系统的稳定性,本文采用基于超前-滞后网络的电网侧电流反馈的主动阻尼方法。主动阻尼方法可以抑制逆变器的谐振并提高系统的稳定性。最后,给出实验结果以验证上述分析。