首页> 外文会议>IEEE International Conference on High Voltage Engineering and Application >Study on the Noise Characteristics of 10kV Vegetable Insulating Oil Transformer
【24h】

Study on the Noise Characteristics of 10kV Vegetable Insulating Oil Transformer

机译:10kV植物绝缘油变压器噪声特性研究

获取原文

摘要

The noise emitted from distribution transformer often disturbs the normal life of people around it, hence it is necessary to research the noise characteristics of the vegetable insulating oil transformer. The characteristic of noise emitted by the 10KV vegetable insulating oil transformer under the condition with no load and different loads were tested in a spacious HV testing hall. As a comparison, the vegetable insulating oil in transformer was replaced by mineral insulating oil, and the noise of the transformer filled with mineral oil has also been measured in the same environment. The experiment results demonstrated that A-weighted sound pressure level of noise emitted from the transformer filled with vegetable insulating oil is about 5~6dB lower than that of noise emitted from the transformer filled with mineral insulating oil. Combined with the characteristics of insulating oil and the classical calculation formula of absorption coefficient, the sound absorption coefficient calculating formula of insulating oil has been derived. Though the calculation, it was found that the sound absorption coefficient of FR3 is about 2 times higher than that of mineral insulating oil. Thus vegetable insulating oil FR3 can reduce the transformer noise better than mineral insulating oil.
机译:从分配变压器发出的噪音通常会扰乱其周围人的正常寿命,因此有必要研究植物绝缘油变压器的噪声特性。在宽敞的HV检测厅中测试了10kV植物绝缘油变压器在没有负载和不同载荷的情况下发出的噪声的特性。作为比较,变压器中的植物绝缘油被矿物绝缘油代替,并且在相同的环境中也已经测量了矿物油的变压器的噪音。实验结果表明,从含有蔬菜绝缘油的变压器发出的加权声压水平比从矿物绝缘油填充的变压器发射的噪音低约5〜6dB。结合绝缘油的特性和吸收系数的经典计算公式,推导出绝缘油的吸声系数计算公式。虽然计算,但发现FR3的吸音系数比矿物绝缘油的吸声系数约为2倍。因此,蔬菜绝缘油FR3可以比矿物绝缘油更好地降低变压器噪音。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号