On-line Monitoring of Current Transformer Dielectric Loss Based on Absolute Measurement

机译:基于绝对测量的电流互感器介质损耗在线监测

获取原文

摘要

CT (Current Transformer) is often used for current conversion in high voltage or extra high voltage grids, so the problem of insulation is very prominent. Since dielectric loss is very effective to judge deterioration and being moistened defects of current transformer, it can be detected by two individual currents. This paper proposes an on-line monitoring system of current transformer's dielectric loss based on absolute measuring method. To guarantee the precision, active zero magnetic flux current sensor is developed. The data in the laboratory demonstrated that the uncertainty of system is less than 0.01%. The field data prove that the variation range of dielectric loss meets the requirements of CT operating normally. Compared to traditional technique, it improves the efficiency and guarantees the accuracy.
机译:CT(电流互感器)通常用于高压或超高压电网中的电流转换,因此绝缘问题非常突出。由于介电损耗对于判断电流互感器的劣化和潮湿缺陷非常有效,因此可以通过两个单独的电流来检测它。本文提出了一种基于绝对测量方法的电流互感器介质损耗在线监测系统。为了保证精度,开发了有源零磁通电流传感器。实验室数据表明,系统的不确定度小于0.01%。现场数据证明,介电损耗的变化范围满足CT正常工作的要求。与传统技术相比,它提高了效率并保证了准确性。