Comparison of Arc Characteristics between 2/4 Coil-type AMF Contact and 3/4 Coil-type AMF Contact

机译:2/4线圈型AMF接触和3/4线圈式AMF接触之间的电弧特性比较

获取原文

摘要

Vacuum circuit breakers are widely used in medium voltage circuit breakers. The 3/4 coil-type axial magnetic field (AMF) contact has passed type test and reaches a nominal rated current of 2500 A. However, there is a higher requirement of the nominal rated current of 3150 A. A new 2/4 coil-type contact was proposed to increase the nominal rated current. But the current interrupting capacity of 2/4 coil-type AMF contact was unknown. The objective of this paper is to compare the vacuum arc characteristics between the 2/4 coil-type AMF contact and the 3/4 coil-type AMF contact to estimate the current interruption capacity of 2/4 coil-type AMF contact. A pair of 2/4 coil-type AMF contact was used in the experiments. Contact diameter was 100 mm, and contact material was CuCr50. Full contact gap was 50 mm, and opening velocity was set as 2.4 m/s within 20 mm after contact separation. A drawn arc experiment was carried out in a L-C discharging circuit. Arcing current was ranged from 5 to 40 kA rms and current frequency was 49.2 Hz. In the experiments, the vacuum arc behaviors were recorded by a high speed CCD camera. The results show that, the resistance of single contact of the 2/4 coil-type AMF contact was $6.29 muOmega$, and the contact resistance of the 3/4 coil-type AMF contact was $8.12 muOmega$. Besides, the intense arc mode duration and the diffuse arc mode duration before the second current zero of the 2/4 coil-type AMF contact and 3/4 coil-type AMF contact was similar. Therefore, the 2/4 coil-type AMF contact could control the high-current vacuum arc as well as the 3/4 coil-type AMF contact. The results suggested that the 2/4 coil-type AMF contact has similar current interrupting capacity with the 3/4 coil-type AMF contact, with a higher carrying capacity of the nominal rated current.
机译:真空断路器广泛用于中压断路器。 3/4线圈型轴向磁场(AMF)触点已通过型式测试,达到标称额定电流为2500A。但是,标称额定电流的要求较高了3150 A.一个新的2/4线圈 - 提出了型接触以增加标称额定电流。但目前的2/4线圈式AMF接触的中断容量未知。本文的目的是比较2/4线圈型AMF接触和3/4线圈型AMF接触之间的真空电弧特性,以估计电流中断容量为2/4线圈型AMF接触。在实验中使用了一对2/4线圈型AMF接触。触头直径为100mm,触头材料是CUCR50。完全接触间隙为50毫米,在接触分离后,打开速度设定为20 mm内的2.4 m / s。在L-C放电电路中进行绘制的电弧实验。电弧电流范围为5至40 kA rms,电流频率为49.2 Hz。在实验中,通过高速CCD摄像机记录真空电弧行为。结果表明,2/4线圈型AMF接触的单次接触的阻力是 $ 6.29 亩欧米茄$ ,3/4线圈型AMF接触的接触电阻是 $ 8.12 mu omega $ 。此外,2/4线圈型AMF接触的第二电流零和3/4线圈型AMF接触前的强弧模式持续时间和漫射电弧模式持续时间相似。因此,2/4线圈型AMF接触可以控制高电流真空弧以及3/4线圈型AMF接触。结果表明,2/4线圈型AMF接触具有类似的电流中断容量,具有3/4线圈型AMF接触,具有较高的标称额定电流承载能力。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号