首页> 外文会议>IEEE Electrical Insulation Conference >Test Set-Up and Preliminary Results of PD Measurements Performed During Thermal Cycles Applied to Different Types of MV Cable Joints
【24h】

Test Set-Up and Preliminary Results of PD Measurements Performed During Thermal Cycles Applied to Different Types of MV Cable Joints

机译:在热循环期间对不同类型的中压电缆接头进行的局部放电测量的测试设置和初步结果

获取原文

摘要

The experimental set-up and the first results of PD measurements performed to evaluate different types of MV cable-joints under electrical and thermal stresses, are discussed in the paper. Twelve cables equipped with different types of joints were connected together to form a ring in short-circuit. The ring was enegized at rated voltage and current. Cycles of temperature having a period of one day have been applied by controlling the current by means of external coils. PD were monitored during the heating and cooling of the cables. Problems related to calibration and signal interference between the different cables, have been examined. The PD inception and the evolution of PD patterns due to the formation of defects in some joints, are discussed.
机译:本文讨论了在电和热应力下进行的评估不同类型的中压电缆接头的实验设置和局部放电测量的第一结果。配备有不同类型接头的十二根电缆连接在一起,形成短路环。在额定电压和电流下对环进行了例示。已经通过外部线圈控制电流来施加为期一天的温度循环。在电缆的加热和冷却过程中对PD进行了监控。已经研究了与不同电缆之间的校准和信号干扰有关的问题。讨论了局部放电的开始以及由于某些接缝处缺陷形成而导致的局部放电模式的演变。