首页> 外文会议>IEEE Power and Energy Society General Meeting >Formal LPV control for transient stability of power systems
【24h】

Formal LPV control for transient stability of power systems

机译:用于电源系统暂态稳定的正式LPV控制

获取原文

摘要

Transient stability analysis of synchronous generators is important for a secure operation of power systems. This paper presents the design and verification of linear-parameter-varying (LPV) controllers to robustly establish transient stability of multi-machine power systems with formal guarantees. First, we transform power systems described by differential algebraic equations (DAEs) into modular LPV systems, such that the interaction and correlation between different machines connected to the grid is preserved. Then, we employ reachability analysis to determine the set of admissible parameter values which is required for the LPV controller synthesis. Afterwards, reachability analysis is also used to formally guarantee that the synthesized controller encloses the time-varying parameters within chosen parameter ranges during transients. Both tasks are solved simultaneously in a systematic fashion. The method is demonstrated on a multi-machine benchmark example to showcase the applicability and scalability of the approach.
机译:同步发电机的暂态稳定性分析对于电力系统的安全运行非常重要。本文提出了线性参数变化(LPV)控制器的设计和验证,以通过正式保证稳健地建立多机电源系统的暂态稳定性。首先,我们将由微分代数方程(DAE)描述的电力系统转换为模块化LPV系统,从而保持连接到电网的不同机器之间的相互作用和相关性。然后,我们使用可达性分析来确定LPV控制器综合所需的一组可接受的参数值。此后,可达性分析也可用于形式上保证合成控制器在瞬态过程中将时变参数封装在所选参数范围内。两项任务以系统的方式同时解决。在多计算机基准示例上演示了该方法,以展示该方法的适用性和可扩展性。