首页> 外文会议>IEEE Power and Energy Society General Meeting >Study on the current differential protection for half-wave-length AC transmission lines
【24h】

Study on the current differential protection for half-wave-length AC transmission lines

机译:半波长交流输电线路电流差动保护的研究

获取原文

摘要

Half-wave-length AC transmission technology is getting more and more attention due to its excellent characteristics such as large transmission capacity and long transmission distance. Traditional current differential protection is not applicable for half-wave-length transmission lines because of the influence of distributed capacitance current. Even if capacitance current compensation algorithm is considered, current differential protection still cannot satisfy requirements. Therefore, algorithms which are immune to capacitance current should be used. Travelling wave differential protection is based on distributed parameter model and is not influenced by capacitance current in theory, but power-frequency component should be used to discriminate internal fault with external fault for half-wave-length transmission line. Simulations verify that in all cases differential current during internal fault is much larger than that during external fault, so travelling wave differential protection is applicable for half-wave-length transmission line.
机译:半波长交流传输技术因其传输容量大,传输距离远等优良特性而受到越来越多的关注。由于分布电容电流的影响,传统的电流差动保护不适用于半波长传输线。即使考虑电容电流补偿算法,电流差动保护仍然不能满足要求。因此,应使用不受电容电流影响的算法。行波差动保护基于分布式参数模型,理论上不受电容电流的影响,但是对于半波长传输线,应使用工频分量来区分内部故障和外部故障。仿真证明,在所有情况下,内部故障期间的差动电流都比外部故障期间的差动电流大得多,因此行波差动保护适用于半波长传输线。