首页> 外文会议>IEEE Power and Energy Society General Meeting >Study on the current differential protection for half-wave-length AC transmission lines
【24h】

Study on the current differential protection for half-wave-length AC transmission lines

机译:半波长AC传输线电流差动保护研究

获取原文
获取外文期刊封面目录资料

摘要

Half-wave-length AC transmission technology is getting more and more attention due to its excellent characteristics such as large transmission capacity and long transmission distance. Traditional current differential protection is not applicable for half-wave-length transmission lines because of the influence of distributed capacitance current. Even if capacitance current compensation algorithm is considered, current differential protection still cannot satisfy requirements. Therefore, algorithms which are immune to capacitance current should be used. Travelling wave differential protection is based on distributed parameter model and is not influenced by capacitance current in theory, but power-frequency component should be used to discriminate internal fault with external fault for half-wave-length transmission line. Simulations verify that in all cases differential current during internal fault is much larger than that during external fault, so travelling wave differential protection is applicable for half-wave-length transmission line.
机译:由于其诸如大传输容量和长传输距离的优异特性,半波长AC传输技术越来越受到关注。由于分布式电容电流的影响,传统的电流差动保护不适用于半波长传输线。即使考虑电容电流补偿算法,即使考虑电容电流补偿算法,当前的差动保护仍然无法满足要求。因此,应使用对电容电流免疫的算法。旅行波差动保护基于分布式参数模型,不受电容电流理论的影响,但应使用功率分量与半波长传输线的外部故障区分内部故障。仿真在内部故障期间的所有情况下,差分电流远远大于外部故障期间的电流,因此行驶波差动保护适用于半波长传输线。