首页> 外文会议>Smart Grid Conference >The estimation of inertia and load damping constants using phasor measurement data
【24h】

The estimation of inertia and load damping constants using phasor measurement data

机译:使用相量测量数据估算惯性和负载阻尼常数

获取原文

摘要

Two very important parameters especially in frequency stability analysis, are inertia constant and equivalent load damping constant of system. Equivalent inertia constant depends on inertia constant of synchronous machines in the grid and load damping factor depends on frequency sensitivity of load, especially induction motors. By appearing wide area monitoring systems (WAMS) based on phasor measurement units, equivalent system frequency response can be obtained with high accuracy. In this paper firstly, the equivalent frequency response is achieved by phasor measurements and then according to the transient and steady state characteristics of the frequency response, the inertia and load damping constants are estimated. The performance of proposed method in estimating the equivalent parameters of the system is investigated under different conditions. The developed method is implemented in IEEE 39-Bus dynamic test grid.
机译:系统的惯性常数和等效负载阻尼常数是两个非常重要的参数,尤其是在频率稳定性分析中。等效惯性常数取决于电网中同步电机的惯性常数,负载阻尼系数取决于负载(尤其是感应电动机)的频率灵敏度。通过出现基于相量测量单位的广域监视系统(WAMS),可以高精度获得等效系统频率响应。本文首先通过相量测量获得等效频率响应,然后根据频率响应的瞬态和稳态特性,估算出惯性和负载阻尼常数。在不同条件下,研究了该方法在估计系统等效参数方面的性能。所开发的方法在IEEE 39总线动态测试网格中实现。