首页> 外文会议>International Symposium on Electrical Machines >The Analysis of the Effectiveness of Standard Protection Devices in Supply Systems Fed from Synchronous Generator Sets
【24h】

The Analysis of the Effectiveness of Standard Protection Devices in Supply Systems Fed from Synchronous Generator Sets

机译:从同步发电机组供给的电源系统中标准保护装置的有效性分析

获取原文

摘要

The paper analyses the effectiveness of the human protection against electric shock in circuits fed from the generator, especially from the backup generation set. Several protection devices of different characteristics were tested in laboratory and new approach to the protection was proposed in TN type wiring (earthed neutral point arrangement). This happened due to the fact that measurements showed that actually used devices do not satisfy protection criteria when full power of the generator is used. This criteria include time criterion - the maximum time of the occurrence of touching overvoltage can occur in less than 0.4 s time period. The proposal include new approach to the short circuit detection, where not only current but also voltage sensing is used. For a IT wiring (system insulated from the ground) “ 0 ” symmetrical component sensing an insulation testing devices are proposed.
机译:本文分析了人类保护对从发电机喂养的电路中触电的有效性,尤其是从备用产生组。在实验室测试了几种不同特性的保护装置,并在TN型布线(接地中性点排列)中提出了新的保护方法。这是由于测量结果显示实际使用的设备在使用发电机的全功率时,实际使用的设备不满足保护标准。该标准包括时间标准 - 触摸过电压发生的最大时间可能在小于0.4的时间段内发生。该提案包括短路检测的新方法,其中不仅使用电流而且使用电压感应。对于IT布线(从地面绝缘)“0”对称分量,提出了绝缘测试装置。