首页> 外文会议>International Institute of Refrigeration;Conference on ammonia and CO2 refrigeration technologies >PHASE CHANGE MATERIAL THERMAL ENERGY STORAGE FOR A LARGE AMMONIA CHILLER/HEAT PUMP SYSTEM
【24h】

PHASE CHANGE MATERIAL THERMAL ENERGY STORAGE FOR A LARGE AMMONIA CHILLER/HEAT PUMP SYSTEM

机译:大型制冷机/热泵系统的相变材料热能存储

获取原文

摘要

Thermal energy storage (TES) can be applied to reduce peak heating and cooling loads in buildings and to improve the performance and reliability of the heat supply system. For short-term TES, phase change materials (PCM) are a compact and efficient alternative. At the Bergen University College in Norway, three ammonia chillers/heat pumps cover the base load for heating and cooling. To reduce the required chiller capacity, PCM cold storage tanks have been installed. The present study evaluates the PCM-TES system in detail through modelling and analysis of measurement data. To gain more understanding of the freezing and melting processes, a dynamic model for the PCM-TES was developed in Dymola. The simulation results were validated towards measurement data. The model allows better understanding of the heat transfer characteristics of the PCM-TES, and enables more sophisticated dimensioning and design of future PCM-TES systems.
机译:可以使用热能存储(TES)来减少建筑物中的峰值供热和制冷负荷,并改善供热系统的性能和可靠性。对于短期TES,相变材料(PCM)是一种紧凑而有效的替代方法。在挪威的卑尔根大学学院,三个氨冷却器/热泵覆盖了用于加热和冷却的基本负荷。为了降低所需的冷却器容量,已安装了PCM冷库。本研究通过对测量数据进行建模和分析来详细评估PCM-TES系统。为了更多地了解冷冻和融化过程,在Dymola中开发了PCM-TES的动态模型。仿真结果针对测量数据进行了验证。该模型可以更好地了解PCM-TES的传热特性,并可以对未来的PCM-TES系统进行更复杂的尺寸设计。