In order to monitor the early fire situation caused by coal spontaneous combustion or cable aging, cable heated, cable overcurrent and other reasons, a dual channel and fast response temperature detection system is designed based on the Raman scattering principle in which anti-stokes signal in back Raman scattering is sensitive to temperature. The performance of the temperature detection system is obtained through experiments. The experimental data shows that the maximum error of temperature measurement is 0.7 °C , the stability is 1 °C in 30 minutes when both channels carry 2.5km sensing fiber, single channel response time is less than 17s and position-calculated error is less than 2m. This system would have a good application prospect in distributed fire detection and early warning under mine.
机译:为了监测煤自燃或电缆老化,电缆发热,电缆过电流等原因引起的早期火灾情况,基于拉曼散射原理设计了双通道快速响应温度检测系统,在该系统中,防焦信号进入返回拉曼散射对温度敏感。温度检测系统的性能是通过实验获得的。实验数据表明,当两个通道都装有2.5km的传感光纤时,温度测量的最大误差为0.7°C,在30分钟内的稳定性为1°C,单通道响应时间小于17s,位置计算误差小于30s。 2m该系统在井下分布式火灾探测与预警中具有良好的应用前景。