首页> 外文会议>International Symposium on Electrical Insulating Materials >Study on insulation deterioration diagnosis by partial discharge in IEC (b) electrode
【24h】

Study on insulation deterioration diagnosis by partial discharge in IEC (b) electrode

机译:IEC(b)电极中局部放电对绝缘劣化诊断的研究

获取原文

摘要

Electric power systems deteriorate with aging while using. Partial discharge (PD) is one of the main factors in electric power system degradation. PD characteristics such as the maximum apparent discharge magnitude (qmax), discharge occurrence frequency (n), pulse mean Φ-q distribution, and Φ-n distribution are important for analyzing the PD phenomenon. This time, PD was generated in the insulation using IEC (b) electrode and its characteristics were analyzed. As a result, the phase angle at which discharge occurs does not depend on frequency and voltage application time, but there was no constant trend in the magnitude of discharge.
机译:电力系统在使用时随着老化而恶化。局部放电(PD)是电力系统劣化的主要因素之一。 PD特性,例如最大表观放电幅度(Qmax),放电发生频率(N),脉冲平均值φ-Q分布和φ-N分布对于分析Pd现象非常重要。这次,使用IEC(B)电极在绝缘中产生Pd,分析其特性。结果,出现放电的相位角不依赖于频率和电压施加时间,但是在放电的幅度下没有恒定的趋势。