首页> 外文会议>International Conference on Electrical Engineering and Computer Science >Evaluation and mitigation of underground gas pipeline coating stress due to nearby lightning stroke
【24h】

Evaluation and mitigation of underground gas pipeline coating stress due to nearby lightning stroke

机译:评估和缓解附近雷击导致的地下天然气管道涂层应力

获取原文
获取外文期刊封面目录资料

摘要

Rapid economic developments have forced power networks and pipeline networks to share the same pathway. Induced voltages and currents appear on pipelines running parallel with high voltage transmission line when the transmission line is hit by lightning strike. In this study, a simulation had been carried out to determine the first lightning stroke effect on an underground pipeline coating stress. CDEGS software was used to solve Maxwell equations; in particular, HIFREQ and FFTSES tools were utilized. A 2-km underground pipeline and a 345-kV transmission line (TL) tower had been modeled. A suitable TL-pipeline distance need to determined based on lightning current, surrounding soil properties, and coating withstand voltage. In addition, horizontal and vertical rods are able to reduce the overvoltage across the coating. The first layer soil resistivity and thickness are important factors to be considered when carrying out mitigation in a non-uniform soil.
机译:经济的飞速发展迫使电力网络和管道网络共享同一路径。当输电线路遭到雷击时,感应电压和电流会出现在与高压输电线路平行的管线上。在这项研究中,已经进行了模拟以确定对地下管道涂层应力的第一个雷击效应。 CDEGS软件用于求解麦克斯韦方程组;特别是,使用了HIFREQ和FFTSES工具。对一条2公里长的地下管道和345 kV输电线路(TL)塔进行了建模。需要根据雷电流,周围土壤的性质和涂层的耐压来确定合适的TL管道距离。此外,水平和垂直杆都可以减少涂层上的过电压。在非均匀土壤中进行减缓处理时,第一层土壤的电阻率和厚度是要考虑的重要因素。