Analysis on lightning impulse test and breakdown reasons of offshore substation GIS

机译:海上变电站GIS雷电冲击试验及故障原因分析

获取原文

摘要

Based on the background of Rudong 150MW offshore wind farm demonstration project, this paper expounds the principle of lightning impulse test and breakdown phenomenon of the offshore GIS equipment, the reason of breakdown is analyzed and the relevant preventive measures and suggestions are given. First of all, the principle of lightning impulse test is described, and then the test platform is built, the results show that both two different voltage degree GIS which are tested are breakdown in different parts. Through the inspection of the discharge points of the two GIS, it is found that the breakdowns in this test are reducible metal gap breakdowns, combined with experimental results and test environment, it is deduced that the breakdowns are due to the metal debris which are introduced in the transport and installation processes of GIS. At last, some relevant suggestions are given to prevent the breakdown and improve the test.
机译:本文以如东150MW海上风电场示范工程为背景,阐述了海上GIS设备的雷电冲击试验原理和故障现象,分析了故障原因,并提出了相应的预防措施和建议。首先介绍了雷电冲击试验的原理,然后建立了雷电冲击试验平台,结果表明,被测的两个不同电压等级的GIS在不同部位都有击穿现象。通过对两个GIS放电点的检查,发现该测试中的击穿是可还原的金属间隙击穿,结合实验结果和测试环境,可以推断出该击穿是由于引入了金属碎片造成的在GIS的运输和安装过程中。最后,提出了一些相关的建议,以防止故障和改进测试。