Amplitude detection of power transformer tank vibrations signal

机译:电力变压器油箱振动信号幅值检测

获取原文

摘要

After switching on an unloaded transformer the time of magnetising current stabilisation is from 5 to 10 s, which clearly corresponds to image of vibrations recorded on the tank surface. The transformer tank vibrations in transient state are caused by vibrations both from windings and from its core. The mechanical quality of the two key elements of the transformer structure may be assessed using vibroacoustic analysis method, analysing the vibrations signal (accelerating of vibrations) recorded with the accelerometer attached to the transformer tank. The subject of the analysis is, in addition to other sizes and parameters, the envelope of the transformer tank vibration signal. Thus, it is important to accurately detect the vibrations amplitude in transient state. As the vibration signal does not meet the condition of AM signal definition, the article proposes an algorithm of a modified AM detector, which was successfully used in vibroacoustic diagnosis of the active part (winding and core) mechanical condition of power transformers.
机译:接通空载变压器后,励磁电流稳定时间为5到10 s,这显然对应于储罐表面记录的振动图像。变压器油箱在瞬态下的振动是由绕组和铁芯的振动引起的。可以使用振动声学分析方法评估变压器结构的两个关键元件的机械质量,分析通过附加在变压器箱上的加速度计记录的振动信号(振动的加速)。除了其他尺寸和参数外,分析的主题还包括变压器油箱振动信号的包络线。因此,重要的是准确检测瞬态的振动幅度。由于振动信号不满足AM信号定义的条件,本文提出了一种改进的AM检测器算法,该算法已成功用于电力变压器有源部分(绕组和铁心)机械状态的振动声诊断。