首页> 外文会议>ASME power conference joint with ICOPE-17 >EXPERIMENTAL STUDY OF HEAT TRANSFER AND RESISTANCE CHARACTERISTICS OF SINGLE H-TYPE AND DOUBLE H-TYPE FINNED TUBES
【24h】

EXPERIMENTAL STUDY OF HEAT TRANSFER AND RESISTANCE CHARACTERISTICS OF SINGLE H-TYPE AND DOUBLE H-TYPE FINNED TUBES

机译:单H型和双H型翅片管传热及阻力特性的实验研究

获取原文

摘要

There are various finned tube heat exchanges with diverse thermo-flow performance being widely applied in the power plants. Wherein, the H-type finned tubes are widely used in the economizer to improve the waste heat utilization efficiency of the coal fired boiler. The experimental studies regarding the heat transfer and resistance characteristics of single H-type and double H-type finned tubes have obtained the thermo-flow performances under different conditions. In addition, the test facility of double channels is specially designed to ensure the test accuracy. Correlations for Euler number Eu, Nusselt number Nu and Performance evaluation index P_(EC) with Reynolds number Re are presented by analyzing the thermo-flow performances of the used bundles. The results show that the single H-type finned tube performs better heat transfer characteristic and relatively worse resistance characteristic than the double H-type finned tube. Consequently, the double H-type finned tube is recommended in the practical application considering the higher manufacturing installation efficiency. (CSPE)
机译:各种翅片管换热器具有多种热流性能,已广泛应用于发电厂。其中,H型翅片管被广泛应用于省煤器,以提高燃煤锅炉的余热利用效率。关于单H型和双H型翅片管的传热和阻力特性的实验研究获得了在不同条件下的热流性能。此外,双通道的测试设备经过专门设计,可确保测试准确性。通过分析所用束的热流性能,得出了欧拉数Eu,努塞尔特数Nu和性能评估指数P_(EC)与雷诺数Re的关系。结果表明,单H型翅片管比双H型翅片管具有更好的传热特性和相对较差的电阻特性。因此,考虑到更高的制造安装效率,在实际应用中建议使用双H型翅片管。 (CSPE)

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号