首页> 外文会议>IEEE/PES Transmission and Distribution Conference and Exposition >Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics
【24h】

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

机译:同时偏出和TAN DELTA测量:电缆诊断中的新技术

获取原文

摘要

In this paper, a focus was placed on the ability to decrease the amount of testing time while monitoring tan delta and PD simultaneously. Healthy and unaged cables do not need to be subjected to unnecessary stresses if no clear abnormalities are detected in diagnostic values. A case study was presented and able to show that testing time and costs can also be reduced for severely aged cable systems. New technology on the market allowing for the simultaneous monitoring of tan delta and partial discharge during monitored withstand testing gives utilities and test personnel time-efficient and cost-optimized testing solutions for new and service-aged cables. The result is a significant reduction in testing time and the ability to realize condition-based and cost-optimized maintenance plans.
机译:在本文中,将重点放在同时监测Tan Delta和PD的同时降低测试时间的能力。如果在诊断价值中未检测到明确的异常,则不需要对健康和平台的电缆进行不必要的应力。提出了一个案例研究,并能够显示用于严重老年电缆系统的测试时间和成本。市场上的新技术允许监控耐受测试期间的TAN DELTA和局部放电的同时监控,为新的和服务老年电缆提供公用事业和测试人员时间效率和成本优化的测试解决方案。结果是测试时间的显着降低以及实现条件为基础和成本优化的维护计划的能力。