摘要

Improper selections of current transformers will result in CT's saturation during fault conditions which can affect protection relays operations. With the absence of clear and practical guidelines for CT's selections, designers are facing great difficulties to ensure proper operations of digital relays. The impact of CT saturation is different for different protection devices and schemes. This paper investigates the influence of CT saturation on over-current digital relays, in distribution systems where loads are relatively smalls and connected to switch-gears with high short circuit levels. A research was performed to verify the operations of instantaneous and time-delayed over-current digital relays to ensure coordination with other devices and safe isolations of faults. It is shown that instantaneous digital relays will perform properly with a relatively small CT's. A criterion for selecting CT's for instantaneous digital over-current relays operations is presented. However, time-delayed over-current relays will be significantly impacted by CT's saturation and special care shall be taken to achieve coordination with other devices.
机译:Improper selections of current transformers will result in CT's saturation during fault conditions which can affect protection relays operations.凭借CT的选择没有明确和实用的准则,设计人员面临巨大困难,以确保数字继电器的正常运行。对于不同的保护装置和方案,CT饱和的影响是不同的。本文研究了CT饱和对过流量数字继电器的影响,其中负载相对较小并连接到具有高短路电平的开关齿轮。进行了研究以验证瞬时和延迟过流数字继电器的操作,以确保与其他设备的协调和断层的安全隔离。结果表明,瞬时数字继电器将以相对较小的CT正确地执行。提出了一种选择CT用于瞬时数字过电流继电器操作的标准。然而,时间延迟过流量继电器将受到CT饱和度的显着影响,并且应采取特殊护理以实现与其他设备的协调。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号