Summary form only given. A new reclosure scheme applied to parallel transmission lines with shunt reactors is proposed to improve the adaptability of the autoreclosure. Detailed analysis of the fault phase voltage is performed to derive the criteria to distinguish the temporary fault from permanent fault. For different types of ground faults, the integral of fault phase's recovery voltage is used for identifying the permanent grounded faults. For different types of cross-line ungrounded faults, the integral of the modulus of fault phase's recovery voltage is used for identifying the permanent cross-line ungrounded faults. Besides, the phase reclosure sequence principle is used for all the fault types. The performance of the proposed scheme is verified by the digital and analog simulation test for a 500-kV parallel transmission line with shunt reactors for several cases on different fault types and fault conditions. The EMTP-based and physical analog simulation results both show that the proposed scheme is effective.
机译:摘要表格仅给出。提出了一种新的刷新方案,其应用于具有分流反应器的平行传输线,以改善自动裂线的适应性。对故障相位电压进行详细分析以导出区分永久性故障的标准。对于不同类型的接地故障,故障相位恢复电压的积分用于识别永久接地故障。对于不同类型的跨线未接地故障,故障相位恢复电压模量的积分用于识别永久性的非线性未处理故障。此外,相位闭合序列原理用于所有故障类型。所提出的方案的性能由用于500 kV并联传输线的数字和模拟仿真测试验证,该试验与分流响应器有几种情况,用于不同的故障类型和故障条件。基于EMTP和物理模拟仿真结果均显示所提出的方案是有效的。