首页> 外文会议>IEEE/PES Transmission and Distribution Conference and Exposition >A new protection scheme to prevent mal-trips due to power swings
【24h】

A new protection scheme to prevent mal-trips due to power swings

机译:一种新的保护方案,以防止由于电力摇摆而导致的抖动

获取原文

摘要

New distance protection algorithms based on mathematical logic blocks are introduced in this paper. The algorithms prevent mal-trips due to power oscillations using additional criteria in combination with traditional distance relaying. These additional criteria are based on symmetrical components and the derivative of the phase angle associated with the current as seen by the relay. A simulation is performed in a eighteen bus system developed by the authors where the performance of the algorithms is analysed. No timer settings as is necessary for conventional Power Swing Detectors are needed. Thus different cycle times of the power oscillations will not affect the performance of the algorithms. Neither an area in the RX-diagram has to be pre-defined which may cause extraordinary difficulties for applications serving long distance transmission lines.
机译:本文介绍了基于数学逻辑块的新距离保护算法。算法导致使用其他标准的功率振荡,与传统的距离中继相结合,防止抖动。这些附加标准基于对称分量和与继电器所见的电流相关联的相角的导数。在分析算法性能的作者开发的18个总线系统中执行模拟。不需要传统的动力摆动检测器所需的定时器设置。因此,电源振荡的不同循环时间不会影响算法的性能。必须预先定义RX-型图中的一个区域,这可能对服务长距离传输线的应用造成非凡的困难。